Grundlegende Informationen.
Modell Nr.
CKG3-160/7.2
Transportpaket
Carton
Spezifikation
CKG3-160/7.2
Warenzeichen
VKSELE
Herkunft
Wenzhou
HS-Code
8536901900
Produktionskapazität
1000pieces/Month
Produktbeschreibung
The main technical parameters
1.Rated voltage:
a:Rated working voltage of main circuit of contactors is 6-7.2KV.
b:Rated voltage of control circuit :AC 200V DC 220V.
c:Auxiliary circuit rated voltage:AC200V,DC220V
d:Rated voltage of release: AC 220C,DC220V
2.Rated current: Main circuit:160A,250A,Rated voltage:AC3 160A,250A,400A.
3.Rated frequency:50/60Hz,
4.operating frequency and working system:
The operating frequency of repetitive short-term working system is 6000h-1
Operating Frequency of Mechanical Holding 30h-'
5.The main contact parameters are shown in the table:
1.Rated voltage:
a:Rated working voltage of main circuit of contactors is 6-7.2KV.
b:Rated voltage of control circuit :AC 200V DC 220V.
c:Auxiliary circuit rated voltage:AC200V,DC220V
d:Rated voltage of release: AC 220C,DC220V
2.Rated current: Main circuit:160A,250A,Rated voltage:AC3 160A,250A,400A.
3.Rated frequency:50/60Hz,
4.operating frequency and working system:
The operating frequency of repetitive short-term working system is 6000h-1
Operating Frequency of Mechanical Holding 30h-'
5.The main contact parameters are shown in the table:
Technical Parameter:
Model | CKG3-160 | CKG3-250 | CKG3-400 | CKG3-630 |
Main circuit Rated vol.(KV) | 7.2/12 | 7.2/12 | 7.2/12 | 7.2/12 |
Main circuit Rated current.(A) | 160 | 250 | 400 | 630 |
Main circuit connection capability (A/100 times) | 1600 | 2500 | 4000 | 6300 |
Main circuit on and off capability (A/10 times) | 1280 | 2000 | 3200 | 5000 |
Limit breaking capacity (A/3 times) | 3200 | 4000 | 4500 | 6300 |
Mechanical life (10,000 times) | 100 | 100 | 100 | 100 |
Mechanical lock life (10,000 times) | 10 | 10 | 10 | 10 |
Main circuit power frequency withstand voltage(KV) | 32/42 | 32/42 | 32/42 | 32/42 |
Auxiliary circuit power frequency withstand voltage(KV) | 2.5 | 2.5 | 2.5 | 2.5 |
Control circuit power frequency withstand voltage(KV) | 2 | 2 | 2 | 2 |
Rated operating frequency(Times/h) | 300 | 300 | 300 | 300 |
Mechanical locking frequency (Times/h) | 30 | 30 | 30 | 30 |
Contact opening distance (mm) | 4±0.5 | 4±0.5 | 4±0.5 | 4±0.5 |
Overtravel (mm) | 1.5±0.3 | 1.5±0.3 | 1.5±0.3 | 1.5±0.3 |
Dimension: